Jablotron JA-111ST-A BUS wired Smoke and Heat detector

Jablotron JA-111ST-A bus wired smoke and heat detector indicates a fire hazard using the built-in LED indicator and acoustic signalling.

It triggers the alarm from the detector but also any other fire detector in the system.

Availability: In stock
SKU
JA-111ST-A
Do you have a question about this product?
Frank

JA-111ST-A BUS wired combined smoke and/or heat detector

The JA-111ST consists of two independent detectors – an optical smoke detector and a heat detector. The optical smoke detector works on the principle of scattered light. It is very sensitive to large dust particles which are present in dense smoke. It is less sensitive to smaller particles generated by the combustion of liquids such as alcohol. That is why the fire detector also contains a built-in heat detector which has a slower reaction but is much better at detecting fire which generates only a small amount of smoke.

The detector communicates wirelessly and it is supplied by batteries (3x 1.5 V AA) for backup.

If the detector is operated without being assigned to a control panel or if communication with the control panel has been lost, it works in an autonomous mode (EN 14604).

The detector indicates a dangerous situation optically with an integrated light and a siren. It is able to acoustically report:

  • a fire alarm detected by the detector itself
  • a fire alarm from the system (alarm triggered by another fire detector)
  • another type of alarm (e.g. an intruder alarm)
  • for alarms reported by the system, sections can be set for which the alarm will be indicated

The product contains two separate detectors – an optical smoke detector and a temperature detector. The optical smoke detector uses the diffused light principle. It is very sensitive to particles that are present in thick smoke. It is less sensitive to small particles produced by the burning of liquids such as e.g. alcohol. Therefore, a heat detector is integrated, which responds better to a fire developing heat quickly with a small amount of smoke.

The detector is not designed for installation in industrial environments.


Technical specifications JA-111ST-A

Power

12 V DC (9 – 15 V)
3 alkaline batteries type LR6 (AA) 1.5 V; 2.4 Ah
3 lithium batteries type FR6 (AA) 1.5 V; 3 Ah
Please note: Batteries are not included

Smoke detection optical light scattering
Smoke detector sensitivity m = 0.11 - 0.13 dB/m
pursuant to EN 14604:2005, EN 54-7
Heat detection class A1 according to EN 54-5
Alarm temperature + 60 °C to +65 °C
Communication range approx. 300 m (unrestricted area)
Dimensions diameter 126 mm, height 52 mm
Weight 150 g
Operating temperature range -10 °C to +65 °C
Also complies with EN 54-25, ETSI EN 300 220, EN 60950-1, EN 50130-4 and EN 55022.
Can be operated according to ERC REC 70-03

Customer Reviews

Blog Posts (1)

Product Questions

JA 151ST-A bij de technische specificaties staat: "Typische levensduur < 3 jaar".
Wordt hiermee de melder bedoeld of de batterijen?

Met vriendelijke groet,
Toon Westgeest
Question by: Toon Westgeest on Feb 24, 2021, 12:42 PM
Hiermee worden de batterijen bedoeld.

MvG
Answer by: Frank Ligthart on Feb 24, 2021, 1:47 PM