Honeywell Notifier ECO1000BREL24L sensor base with relay (24V). The relay base has been designed to provide interfacing between an ECO1000 detector and 24V system Fire Control Panels.
The ECO1000BREL24L has been designed to provide interfacing between an ECO1000 detector and 24V system Fire Control Panels or Power Supplies that require an external contact to activate an ancillary piece of equipment. The relay is controlled directly from the ECO1000 detector. Therefore, in an alarm condition both the detector and relay base will latch into alarm, and can only be reset by removing the supply voltage from the detector.
A break off tab allows the base to be connected to a range of Fire Control Panels. This tab should be broken when there is no current limiting resistor, such as when used as a stand-alone system powered by a 24V supply.